Withdrawable circuit breaker with guide frame, IEC 60947-2, frame size 2, 3-poles, In=3200A up to 690V AC 50/60Hz, breaking capacity S Icu=66/50kA at 500/690V, Trip unit ETU600 LSI upgrade ready , colordisplay, bluetooth and USB interface, Protection LT, ST, INST, N-protection required an external N-sensor, incl. trip alarm switch (1xCO), rear connection horizontal, guide frame with shutter and w/o position signalling switch, able to communication, with manual and motorized operating mechanism (M) 208-240 V AC / 220-250 V DC, Storage status and ready-to- close signaling switches, Auxiliary switches 4NO+4NC, Closing coil (CC) 100% OP 24-30 V DC, applicable for continuous duty, Remote trip alarm reset (RR) 24-30 V DC for momentary duty, without 2nd shunt trip, Shunt trip (ST) 100% OP 24-30 V DC, suitable for continuous duty, Option C01 = Operations counter for circuit breaker option M71 = changeover to CC/ST without communication capability Option N03 = Secondary disconnect system with screw type terminals instead of Push-In technology. Option R55 = Mutual mechanical interlocking with 2 m bowden cable for circuit breakers in withdraw- able design necessary once for each circuit breaker. Option S07 = Locking provision against unauthorized closing Secured Open; for padlock device Padlocks are not included.